step by step for finding Z1_bus
Bus1 to reference
Z1_bus= 
    0.15  

Bus2 to Bus1
Z1_bus= 
    0.15    0.15  
    0.15    0.35  

Bus2 to Reference
Z1_bus= 
    0.105i    0.045i  
    0.045i    0.105i  

Z2_bus= 
    0.105i    0.045i  
    0.045i    0.105i  

step by step for finding Z0_bus

Bus1 to reference 
Z0_bus= 
    0.05  

Bus1 to Bus1 
Z0_bus= 
    0.05    0.05  
    0.05    0.45  

Bus2 to reference 
Z0_bus= 
    0.045i    0.005i  
    0.005i    0.045i  



Fault current calculation
If1_1 = -j3.92157
Fault current=If1=3If1_1=-j11.8




Short circuit current on the transmission line in all the three phases

If_a_12= 
    2.745098i  

If_b_12= 
  - 2.0377068 + 0.3921569i  

If_b_12= 
  - 2.0377068 + 0.3921569i  



short circuit current phase(a) of the generator
Ifa_G = -j4.75465


Voltage of the healthy phases of the bus 1
Vf_b_1=-0.2647 - j0.86603
Vf_c_1=-0.2647 + j0.86603 