 example 4 16   
 load current i1 962.24-721.68A 
 load current current on improved power factor 962.24-316.27jA 
 (a)   
 line current of 400V capacitor bank 405.41A
 line current of 2200 capacitor bank 73.71A 
 phase current of capacitor bank 42.56A 
 reactance 51.70 
 capacitance 61.57F*10^(-6) 
 (b)   
 kVA rating 280.9kVA 
 kVA rating of transformer to convert 400V to 2200V will be the same as the kVA rating of capacitor bankpercentage reduction in losses 29 percent 
 (d)   
 phase current 234.1A 
 reactance 1.71ohm 
 capasitance 1862.61*10^-6F 
 ratio of capacitance 0.033 