Total resistance per phase = 20.00 ohm 

Total reactance per phase = 40.00 ohm 

Total susceptance per phase = 0.00025 ohm 

Phase impedance = 20.00+j(40.00) 

Recieving end voltage = 63509 V 

Load current = 116.64 A 

Impedance per phase = 20.00+j(40.00)

Receiving end voltage is the reference phasor = 63508.53+j0 

Load current = 104.97+j(-50.84) 

Voltage across C = 65575.07+j(1591.05) 

Charging current = -0.40+j(16.39) 

Sending end current = 104.58+j(-34.45) 

Sending end current magnitude = 110.10 A 

Sending end voltage = 67309.76+j(3338.08) 

Sending end voltage magnitude = 67392.48 V 

Line value of sending end voltage = 116.73 V 

Total line losses for three phases = 0.701 MW 

Transmission efficiency = 96.61 % 