(i) When synchronous motor runs at 0.8 pf lag:

	 Input to synchronous motor = 79.09 kW 
	 Lagging kVAR taken by synchronous motor = 59.31 kVAR 

	 Input to induction motor = 179.39 kW 
	 Lagging kVAR taken by induction motor = 179.44 kVAR 

	 Total lagging kVAR = 238.76 kVAR 
	 Total active power = 288.48 kW 
	 Total kVA = 374.47 kVA 
	 Annual kVA demand charges = Rs. 37446.55 
	 Energy consumed per year = 2527052.08 kWh 
	 Annual energy charges = Rs. 151623.13 
	 Total annual bill = Rs. 189069.67 

(ii) When synchronous motor runs at 0.8 pf lead:

	 Net lagging kVAR = 120.13 kVAR 
	 Total active power = 288.48 kW 
	 Total kVA = 312.49 kVA 
	 Annual kVA demand charges = Rs. 31248.96 
	 Energy consumed per year = 2527052.08 kWh 
	 Annual energy charges = Rs. 151623.13 
	 Total annual bill = Rs. 182872.09 

Annual saving = Rs. 6198 