% reactance of alternator = 10.00 % 

% reactance of transformer = 10.00 % 

% reactance of transmission line = 40.00 % 

% resistance of transmission line = 10.00 % 

(i) Total % reactance = 60.00 % 

    Total % resistance = 10.00 % 

    % impedance from generator nuetral upto fault point = 60.83 % 

    Short circuit kva = 16440 kVA 

(ii) % impedance from generator nuetral upto fault point = 20.00 % 

     Short circuit kva = 50000 kVA 