Total resistance / phase = 10.00 ohm 

Total reactance / phase = 50.00 ohm 

Total susceptance / phase = 0.001000 S 

Recieving end voltage = 38105 V 

Load current = 194.39 A 

Recieving end voltage phasor = 38105+j0 

Load current = 174.95+j(-84.73) 

Charging current at load end = j(19.05) 

Line current = 174.95+j(-65.68) 

Sending end voltage = 43138.76+j(8090.91) 

Line to line sending end voltage = 76.02 kV 

Charging current at sending end = -4.05+j(21.57) 

Sending end current = 170.91+j(-44.11) A 

Sending end current = 176.51 A 

(i) Angle between Vr and Vs = 10.62 degrees 

    Angle between Vr and Is = -14.47 degrees 

    Angle between Is and Vs = 25.10 degrees 

    Sending end power factor = 0.91 

(ii) % Voltage regulation = 15.18 % 

(iii) Sending end power = 21.05 MW 

      Transmission efficiency = 95.02 % 