 ans  =
Total resistance per phase = 10.00 ohm 

Total reactance per phase = 20.00 ohm 

Total susceptance per phase = 0.00040 ohm 

Recieving end voltage = 38105 V 

Load current = 109.35 A 

Impedance per phase = 10.00+j20.00 

Receiving end voltage is the reference phasor = 38105.12+j0 

Load current = 87.48+j-65.61 

Voltage across C = 39198.58+j546.73 

Charging current = -0.22+j15.68 

Sending end current = 87.26+j-49.93 

Sending end current magnitude = 100.53 A 

Sending end voltage = 40134.16+j1169.68 

Sending end voltage magnitude = 69.54 V 

Phase angle between Vr and Vs = 1.67 degrees 

Phase angle between Vr and Is = 29.78 degrees 

Sending end power factor angle = 31.45 degrees 

Sending end power factor = 0.85 

Sending end power = 10330.954 kW 

Power delivered = 10000 kW 

Transmission efficiency = 96.80 % 