 Given line-line voltage = 4400.0000 V 



 Impedance of the load = 20.0000  /_30.0000 ohms 



 Impedance of the line = 1.4000  /_75.0000 ohms 



 Base Voltage = 4400.0000 V 

 

 Base Current = 127.0000 V 



 Base Impedance = 20.0027 V 



 Van = 2540.3412  /_ 0.0000 V 



 Ian = 127.0171  /_ -30.0000 V 

 
 Per-unit Quantities   


 Per Unit line-line voltage = 1.0000  /_0.0000 per unit 



 Per Unit line-neutral current = 1.0001  /_-30.0000 per unit 



 Per Unit line-neutral voltage = 1.0507  /_2.7002 per unit 



 Per Unit line impedance  = 0.0700  /_75.0000 per unit 



 Per Unit load impedance = 0.9999  /_30.0000 per unit 



 The line to neutral voltage at the substation , VLN = 2669.0452 /_0.0000 V 



 The magnitude of the voltage at the substation bus , VLL= 4622.9218 V 