 Under maximum load the currents on 345-kV and 34.5-kV side of the transformer respectively in A   
 
    1004.0874  
 
    100.40874  
 
 Current flowing through the differential relay from 34.5-kV side   
 
    5.0204371  
 
 To balance the above current each of the secondary windings of the delta connected CTs should have a current(in A) of   
 
    2.8867513  
 
 CT ratios in secondary for the above currents   
 
    34.782609  
 
 CT secondary currents for ratio 200/5 on the secondary side of 345-kV will be   
 
    2.5102186  
 
 Line currents from CTs to differential relays   
 
    4.3478261  
 
 Required turns ratio for the three auxillary CTs uses is   
 
    1.1547005  