 The positive sequnce impedances of the three line in ohms in the order line 1-2,line 2-3,line 2-4 are   
 
    3.2 + 32.i  
 
    3.2 + 32.i  
 
    4.8 + 48.i  
 
 Maximum load current in A   
 
    209.18488  
 
 System Voltage to neutral   
 
    79674.337  
 
 cvt ratio = 1089.1/1   
 
 The impedance of the lines as seen by R12 in ohms in the order line 1-2,line 2-3,line 2-4 are   
 
    0.1076382 + 1.0763817i  
 
    0.1076382 + 1.0763817i  
 
    0.1614573 + 1.6145726i  
 
 Impedance of load current   
 
    10.249307 + 7.68698i  
 
 Setting of zone one on secondary in ohms   
 
    0.0861105 + 0.8611054i  
 
 Setting of zone two on secondary in ohms   
 
    0.1291658 + 1.2916581i  
 
 Setting of zone three on secondary in ohms   
 
    0.3013869 + 3.0138688i  