 One third of minimum fault current in A   
 
    55.023923  
 
 For CT ratio 50/5 resulting relay current in A will be   
 
    5.0021749  
 
 Settings for relay R4   
 
 CT ratio = 50:5   
 
 Pick up setting in A = 5   
 
 Time-dial setting = 1/2   
 
 The relay current of both R3 and R4 for higest fault current seen by R4   
 
    30.065788  
 
 Operating time for R4 with time dial setting 1/2 in sec is   
 
    0.135  
 
 Required operating time of relay R3   
 
    0.435  
 
 Settings for relay R3   
 
 CT ratio = 50:5   
 
 Pick up setting in A = 5   
 
 Time-dial setting = 2   
 
 Pickup setting in A   
 
    3.9655172  
 
 Reatio of relay current to picup setting in A for max fault current through R3   
 
    8.6134419  
 
 Operating time of R2 in sec   
 
    0.61  
 
 For backing up R3 the ratio of relay current to pickup setting of R2 in A   
 
    5.3834012  
 
 Settings for relay R2   
 
 CT ratio = 100:5   
 
 Pick up setting in A = 4   
 
 Time-dial setting = 2.6   
 
 Settings for relay R1   
 
 CT ratio = 100:5   
 
 Pick up setting in A = 5   
 
 Time-dial setting = 2.9   