 Input Rating of the single equivalent motor = 5001117 kVA 
 
 For Motor   

X11 = 0.3 per unit
 X_2 = 0.3 per unit
 X_0 = 0.06 per unit
 3X_n = 0.09 per unit

 The equivalent generator reactance from neutral to ground in the zero-sequence network = 0.15 per unit

 Base current in motor circuit = 7217 


 Prefault current through line a = 0.565 - j0.350 per unit



 Z1 = j0.12 per unit
 Z2 = j0.12 per unit
 Z0 = j0.15 per unit

 Current Ia in fault = -j7.693 per unit 
 
 Currents in the line at the fault from the transformer in the order Ia,Ib,Ic in per unit are   
 
  - 3.0768173i              
    6.661D-16 + 1.5384086i  
    6.661D-16 + 1.5384086i  
 
 Currents in the line at the fault from the transformer in the order Ia,Ib,Ic in A are   
 
    22205.016  
    11102.508  
    11102.508  
 
 Currents in the line at the fault from the motor in the order Ia,Ib,Ic in per unit are   
 
  - 4.6159135i              
    3.331D-16 - 1.5384086i  
    3.331D-16 - 1.5384086i  
 
 Currents in the line at the fault from the motor in the order Ia,Ib,Ic in A are   
 
    33312.486  
    11102.508  
    11102.508  
 
 Per Units currents in the order I_A,I_B,I_C in per unit are   
 
    0  
 
    8.882D-16 + 2.6646019i  
 
  - 8.882D-16 - 2.6646019i  
 
 Per Units currents in the order I_A,I_B,I_C in A are   
 
    0.  
 
    2775.627  
 
    2775.627  
 
 Under loaded conditions   
 
 Current from transformer to the fault phase a   
 
    0.5651515 - 1.8886581i  
 
 Current from motor to the fault phase a   
 
  - 0.5651515 - 0.6755855i  