 Fault current in per unit = -j8 

 Fault current in amperes = 16735 

 Subtransient current through breaker A in per unit is -j7 

 Subtransient current through breaker A in amperes is 14643 
 
 Symmetrical Short circuit current to be interrupted in A   
 
    12551.093  
 
 The short circuit current rating of breakers must be atleast(in amperes)   
 
    13945.659  

 The required capability of 13946 A is well below 80 percent of 19993 A and the breaker is suitable with respect to the short-circuit current